    CHAUVIN ARNOUX CA8336 Power and Energy Quality Analyser

    The CA8336 is designed for test and maintenance teams working in industrial or administrative buildings, the Qualistar+ C.A 8336 can be used to obtain a snapshot of the main features characterizing the quality of the electrical network. This analyser's functions make it the ideal instrument for preventive or corrective maintenance. It can also be used to perform a complete energy survey of an installation. For sizing installations or troubleshooting switching faults, the C.A 8336 is equipped with Inrush and TrueInrush functions. Easy to handle and particularly compact, this instrument also offers a large number of calculated values and several processing functions. The C.A 8336 is equipped with 4 voltage measurement channels and 4 current measurement channels. The C.A 8336 captures and records all the parameters, transients, alarms and waveforms simultaneously.

    When current sensors are connected to the C.A 8336, it recognizes them automatically. It also offers the possibility of mixing different types of current sensors and configuration of the ratios allows direct reading of the measurements. Specially designed for work in the field. The multiple functions of the Qualistar+ C.A 8336 make it a versatile instrument. It is suitable for applications up to 1,000 V in CAT III and 600 V in CAT IV.

    To see a video demonstration, please press here.

    Software

    The measurements obtained with the Qualistar models can be processed using two software tools: PAT delivered as standard and Dataview®, available as an option. They allow configuration, transfers, processing and analysis. In addition, Dataview® offers the possibility of generating reports according to the voltage quality standards.

    4 Ampflex A193 Clamps

    A193-450 Ampflex current sensor 200mA to 10kA measurement range. 140mm diameter. Suitable for all CA833X, CA8435 and PEL10X range of testers.

    Features

    Direct access to the main functions (configuration, etc.)

    Direct access to the measurements (harmonics, flicker, etc.)

    Voltage/current inputs equipped with colour-coded inserts

    Large colour TFT screen for easy reading

    Battery life: 13 hrs

    The multiple functions of the Qualistar+ C.A 8336 make it a versatile instrument. It is suitable for applications up to 1,000 V in CAT III and 600 V in CAT IV.

    Item Specification

    Alarms 10,000 of 40 different types
    Peak Yes
    Vectorial Representation Automatic
    Display Colour ¼ VGA TFT screen, 320 x 240, diagonal 148 mm
    Capture of screens and curves 50
    Electrical safety IEC 61010 1,000 V CAT III / 600 V CAT IV
    Protection IP53 / IK08
    Languages More than 27
    Communication interface USB
    Battery life Up to 13 hours
    Power supply 9.6 V NiMH rechargeable battery or external mains charger
    Dimensions 240 x 180 x 55 mm
    Weight 1.9 kg

    Additional Details