• Product Description

    The HPAT600 HandyPAT is an easy to use battery powered, hand held PAT tester that is ideal for testing all types of portable appliances. The tester is supplied with rechargeable batteries for low running costs and a mains and in-car charger for convenience. Whilst recharging, the HPAT can still be operated from the mains supply ensuring maximum productivity at all times.

    It has a fast automatic one button test sequence or a simple to operate manual mode useful for diagnostics and can be used for testing both 240V and 110V appliances with the optional TL157 adaptor lead.

    In automatic mode, the HPAT600 will routinely run through a selected test sequence without any further user interaction unless a failure is encountered. In manual mode, a connection diagram for the selected test type is shown on the display and each step of a test requires user confirmation by a press of the OK button.

    The user can select either the standard 500V insulation test or a 250V option which is required for testing appliances with surge protected circuits. The pass levels can also be adjusted which is particularly useful for testing appliances with long power cords or long extension leads. The HPAT600 stores test data for up to 200 appliances for on-screen recall, making it easy to review earlier results when on-site. This function is not for downloading to a PC. In addition to the mandatory safety tests, the HPAT600 can also be used to carry out a simulated load test to check the appliance is in working order and to confirm the integrity of the fuse

    HPAT600 delivery contents include an extension lead adaptor, an earth bond probe with clip, a mains charger, 6xAA rechargeable batteries and a “Test & Go” carry case with separate pocket for accessories. In addition, the HPAT600 also includes an in-car charger and a handy null pin key fob.

    A comprehensive range of optional adaptor leads are available enabling 110V appliance testing and testing of equipment terminated with 3 phase plugs.

    The HPAT600/2 has a new high contrast backlit display.

    Compact portable design with backlit display

    Class I, Class II & power lead tests

    Automatic and manual testing with adjustable limits

    Measured values with clear PASS/FAIL indication

    Suitable for testing 240V and 110V appliances

    Simulated load test

    Built-in memory for on-screen recall of results

    I.T. safe 200mA earth bond test

    Selectable 250V / 500V insulation test

    Includes carry case, mains & in-car chargers and essential accessories

    Features

    Simple automatic & manual testing

    Pass/Fail indicators with test results

    Class I, Class II & power lead tests

    200mA earth bond test – I.T. Safe

    250V / 500V insulation test

    Backlit display with on-board help

    Memory with on-screen recall

    Rechargeable, mains or in-car

    What Is Included:

    Includes TC57 carry case

    PSUHPAT230 mains charger

    rechargeable batteries

    EX332 IEC lead

    TL67 earth bond probe

    PSUHPAT12 in-car charger

    Earth null adaptor

    Manual

    Item Specification

    Earth continuity Test current: 200mA DC
     Range: 0-19.99Ω
     Resolution: 0.01Ω
     Accuracy: ± (5% rdg + 2 dgt)
     Default pass level: Class I ≤ 0.1Ω, Lead ≤ 0.1Ω
     User selectable pass levels: 0.1Ω to 0.9Ω in 0.1 steps
    Insulation Test Voltage: 250V/500V DC selectable
     Test current: 1.5mA
     Ranges: 2.00MΩ, 20.0MΩ, 200MΩ
     Resolution: 0.01MΩ
     Accuracy: <100MΩ ± (5% rdg + 2 dgt), >100MΩ ± (10% rdg + 2 dgt)
    Default pass level Lead: ≥ 1.0 MΩ
     Class I: ≥ 1.0 MΩ
     Class II: ≥ 2.0 MΩ
    User selectable pass level 0.3MΩ to 1MΩ in 0.1MΩ steps
     1MΩ to 10MΩ in 1MΩ steps
    Fuse test Voltage: 4V DC (open circuit)
     Current: 200mA DC (short circuit)
     Pass level: >2mA
    Simulated load test Voltage: 4V DC (open circuit)  Current: 200mA DC (short circuit)
     Accuracy: ± (5% rdg + 2 dgt)
    Overload protection 300V AC/DC
    Complies with BS EN 61010
    Temperature range -10 to 40°C
    Supply 6 x 1.2V AA NiMH rechargeable batteries 1800mAh
    Dimensions 90 x 210 x 54mm
    Weight 700g (inc batteries & leads)

    Additional Details

    Type PAT Tester