• Product Description

    Di-Log's lightweight, portable ApplianceTest DLPT2PAT tester is unique in its range of safety tests. The ApplianceTest DLPT2 will perform all of the tests required by the IEE Code of Practice, including RCD trip, protective conductor current and touch current where required. The unit also includes a 250V DC insulation test suitable for testing sensitive electrical appliances and surge protected leads.

    The Appliance Test DLPT2 is ideal for ensuring that all workplace electrical equipment does not pose a danger to users -including three-phase machinery*. As a result, 3-phase industrial plant and equipment used in factories, workshops, schools and colleges can all be tested safely and effectively.

    The unique range of tests incorporated in this lightweight and highly versatile instrument means that most workplace appliances can be tested using long life battery power. However, when protective conductor current or touch current measurements are required, simply connecting a mains supply will automatically select the correct test sequence.

    The Appliance Test DLPT2 is designed for ease of use and carries out all electrical safety tests against pre-set limits with measured test results and clear PASS/FAIL indication on a large display.

    The Appliance Test DLPT2 is an easy-to-use tester which is ideal for those who need to test a wide range of electrical equipment.

    *For 3 phase and RCD testing, accessories are required.

    *Currently, the mobile app feature is not available on the DLPT2

    Item Specification

    Earth continuity   0.01 Ω - 19.99 Ω, 200mA minimum into 2Ω
    Pass value Pass value 0.2 Ω
    Insulation resistance 0.01 MΩ - 19.99 MΩ, 250/500VDC @1mA nominal
    Pass value 1 MΩ Class I, 2 MΩ Class II
    Equivalent leakage 0.15mA to 9.99mA, 40V nominal AC
    Pass value 0.75mA CL I / 0.25mA CL II
    IEC lead test 5V DC nominal
    IEC checks Checks Live/Neutral for c/c, s/c, and crossed
    Protective conductor current (earth leakage) 0.15mA to 9.99mA, Supply voltage, max current 13A
    Pass value 0.75 mA/3.50mA user selectable with 0.75mA as default
    Touch current 0.10mA to 5.00mA, Supply voltage, max current 13A
    Pass value 0.25mA
    RCD trip time 30mA rms, 0ms to 500ms @ 0 & 180 Degrees auto switched
    Pass value 200ms
    3 phase differential leakage current *Requires 3 phase adaptor accessory 0.10mA to 9.99mA, 3 phase supply voltage
    Pass value 3.5mA
    Power socket check 225 - 254V AC  max current 13A
    Line potential phase to earth
    Line potential phase to neutral
    Line potential neutral to earth
    Power supply 6 x AA batteries / 225-245V AC for powered tests
    Dimensions 260 x 100 x 55 mm
    Weight 800 g

    Additional Details

    Type PAT Tester