• Product Description

    The PEL 105 logger is particularly simple to use with an all-terrain IP67 casing capable of withstanding shocks, UV rays and extreme temperatures.

    It is ideal for outdoor installation directly on an electricity pole. With its 1,000 V CAT IV safety rating, it can be used for measurements on all LV networks, including measurements of the neutral-earth voltage and the neutral current. This stand-alone instrument is equipped with a selfpowering system via its voltage inputs up to 1,000 V. The PEL 105 offers 5 voltage inputs and 4 current inputs. Compatible with a large number of current sensors to make it easier to use, it also recognizes the sensors automatically.

    The PEL 105 can be used to measure, record and analyse the power values (W, var, VA) and energy values (kWh, kvarh, kVAh). At the same time, they record the PF and the DPF. Recording is continuous with a sampling interval of 200 ms.

    Please press the link below for energy efficiency video

    https://youtu.be/7L_teYTIj98

    Features

    5 voltage inputs & 4 current inputs

    All-terrain shockproof casing resistant to UV light and high temperatures

    Ideal for mounting on electricity poles

    Self-powered by its voltage inputs up to 1,000 V

    Continuous recording at 200 ms intervals

    Measurements in compliance with IEEE 1459

    What Is Included:

    1 PEL105 logger delivered with 5 x 3 m black silicone cables,

    straight banana / straight banana, 5 black 1,000 V CAT IV

    crocodile clips, 1 set of inserts/rings, 4 AmpFLEX® IP67 A196

    3 m long, 1 set of waterproof plugs, 1 SD card, 1 USB cable,

    1 bag, 1 safety datasheet, a quick start-up guide and an

    operating manual on USB key.

    Item Specification

    Display With backlit triple digital display
    Type of installation Single-phase, split-phase, three-phase with or without neutral and many other specific configurations
    Number of inputs 5 voltage inputs, 4 current inputs
    Number of channels 4 voltage channels, 4 current channels
    Measurements 
    Network frequency DC, 50 Hz, 60 Hz and 400 Hz
    Voltage (measurement ranges / best accuracy) 10.00 V to 1,000 VAC @ 50/60 Hz, or 600 VAC @ 400 Hz / 1,000 VDC
    Current (depending on sensors) (measurement ranges) 5 mAAC to 10 kAAC / 50 mADC to 5 kADC
    Calculated measurements
    Ratio Up to 650,000 V / up to 25,000 A
    Power 20 W to 10 GW / 20 var to 10 Gvar / 20 VA to 10 GVA
    Energy Up to 4 EWh / 4 EVAh / 4 Evarh (E = 1018)
    Phase cos φ, tan Φ, PF
    Harmonics Up to the 50th order
    Additional functions
    Phase sequence Indication of valid connection
    Min / Max On all quantities
    Recording
    Sampling rate/ Acquisition rate / Aggregation 128 samples/period - 5 measurements/s - from 1 min to 1 hr
    Storage SD card, 8 GB (up to 32 GB with SD-HC card)
    Communication Ethernet, Bluetooth, Wifi and USB
    Power supply Self-powered internally from 94 to 1,000 V @ 50-60 Hz & 400 Hz / DC
    Safety IEC 61010 1,000 V CAT IV
    Mechanical specifications
    Dimensions 245 x 270 x 180 mm
    Weight < 4 kg
    Protection IP 67

    Additional Details

    Type Power Quality Analysers