• Product Description

    The simple one button, one test interface for testing both 240V and 110V appliances speeds up testing. It performs the mandatory tests for earth bond and insulation and has the added benefits of run current, run leakage and flash test making it ideal for both routine onsite testing, tool hire checks and workshop service and repair applications. The EPAT2100 is capable of full high current bond testing at 25A and 8A or can be set to 200mA for safe testing of sensitive IT equipment.

    It can be powered by a 110V or 240V supply which enables the run current or run leakage test to be performed without the need for connection to an external power source. The TL150 110V adaptor is included to enable connection to a 110V supply.

    The Easypat2100 has a built in lead tester for testing IEC power leads and includes all accessories for fast testing of mains extension leads. The lead tester will perform a polarity test and clearly indicates any faults found during the test.

    Features

    Suitable for onsite PAT testing and workshop applications

    Simple one button, one test operation

    Fast and easy Class I & Class II appliance testing

    Tests both 240V and 110V appliances based on supply voltage

    High and low current earth bond tests at 8A, 25A and 200mA

    Insulation test at 500V

    Extension & IEC lead testing built-in

    Run current & leakage tests for full appliance testing

    Hipot / Flash testing for tool hire and workshop service & repair applications

    Mains powered 110V/240V with instant on

    Hard case with storage and removable top

    Item Specification

    Earth Bond Test Test Currents: 8A AC, 25A AC, +/- 200mA DC (IT Safe) Display Range: 0.00Ω - 1.99Ω
    Insulation Resistance Test Voltage: 500V DC
    Display Range: 0 - 19.9MΩ
    Run Current Test Range: 0 - 19.9mA
    Usable Range: 0 - 13.0A
    Earth Leakage Test Range: 0 - 19.9mA
    Flash Test Test Voltage: Class I - 1.5kV AC; Class II - 3.0kV AC
    Display Range: 0 - 19.9mA AC
    Usable Range: 0 - 3mA (current trip @ 4mA nominal)
    Fuse Test Test Voltage: 6V AC Nominal
    Over range Threshold: 10kΩ nominal
    Zero Range Threshold: 800kΩ nominal
    IEC & Extension Lead Test Earth Continuity: 8A AC, 25A AC
    Insulation Test: 500V DC
    Wiring Test: Live, Neutral Continuity & Polarity

    Additional Details

    Colour Yellow
    Industry Electric
    Type PAT Tester